Model And Meanings

Characteristic
![]() |
![]() |
![]() |
![]() |
| Short Circuit Protection | Overload Protection | Earth leakage protection | Arc protection |
![]() |
![]() |
![]() |
![]() |
| Flame Retardant Material | High Breaking Capacity | Short arcing | Multiple Wiring Options |
Breaking Characteristic Curve

Technical Parameters
| Standard | EN60947-2、AS/NZS IEC 60947.2、GB/T14048.2 | |||
| Pole | 1P | 2P | 3P | 4P |
| Rated Working Voltage Ue | 230V AC/300V DC | 400V AC/600V DC | 400V AC/900V DC | 400V AC/1200V DC |
| Maximum current of the shell frame | 125A | |||
| Rated Current In | 80A、100A、125A | |||
| Rated Insulation Voltage Ui | 1200V | |||
| Rated impulse withstand voltage Uimp | 8kV | |||
| Tripping Characteristic | B/C | |||
| Tripping Type | Thermomagnetic | |||
| Limiting Breaking Capacity Icu | 6kA | |||
| Operational Breaking Capacity Ics | 6kA | |||
| Electrical Life | |
| Actual Average Value | 1000 times |
| Standard Specified Value | 300 times |
| Mechanical Life | |
| Actual Average Value | ≥ 15000 times |
| Standard Specified Value | 9700 times |
| Overvoltage category | III |
| Pollution degree | 3 |
| Protection Level | IP40; Wiring port IP20 |
| Resistance to high humidity and heat | Class 2 |
| Relative humidity | ≤ 95 % |
| Vibration-resistant | In accordance with IEC60068-2-6 |
| Mechanical Shock Resistance Parameters | In accordance with IEC60068-2-27 |
| Wiring Capacity | 2.5~35mm² |
| Wiring Torque | 3.0Nm |
| Operating Ambient Temperature | -30℃ ~ +70℃ |
| Storage Ambient Temperature | -40℃ ~ +85℃ |
| Installation Method | DIN35 |
| Altitude | ≤ 2000m |
| Weight | 0.13kg/ Pole |
| Dimension | |
| Length | 85mm |
| Width | 72mm(4P)、54mm(3P)、36mm(2P)、18mm(1P) |
| Height | Max 78mm |
Technical Specifications for Auxiliary Contacts OF
| Item | Parameter |
| Contact Breaking Capacity | AC13: Ie=3A; Ue=250V |
| AC15: Ie=2A; Ue=250V | |
| DC12: Ie=0.5A; Ue=110V | |
| Minimum Operating Voltage | 5V |
| Minimum Operating Current | 10mA |
| Rated Insulation Voltage | 500V |
| Rated Limiting Short-circuit Current lk | 1000A |
| Conventional Thermal Current Ith | 4A |
| Mechanical Life | 10000 times |
| Electrical Life | 4000 times |
| Wiring Torque | 0.3~0.8 N·m |
| Wiring Capacity | 1×1.0~1×2.5mm² |
| Contact Quantity | 1NO, 1NC |
| Operating Temperature Range | -30℃ ~ +70℃ |
| Environmental Conditions | There should be no substances that pose an explosion hazard, nor any harmful gases or conductive dust that could corrode or damage the insulation. |
| Assembly Location | Left side of circuit breaker |
| Installation Requirements | Mounted on standard DIN35mm rail |
Packaging and Storage
| Current | Pole | Pcs/Box | Boxes/Carton | Cartons/Pallet | Storage Instruction |
| 80A | 1P | 12 | 10 | 80 | The product should be stored in a well-ventilated warehouse. Relative humidity should not exceed 80%, and the ambient temperature should be between -40℃ and +85℃. Additionally, the storage area should be free of acidic, alkaline, and corrosive gases. |
| 80A | 2P | 6 | 10 | 80 | |
| 80A | 3P | 4 | 10 | 80 | |
| 80A | 4P | 3 | 10 | 80 |
Derating Factor
| Temperature | Rated current factor |
| -30℃ | 1.242 |
| -25℃ | 1.223 |
| -20℃ | 1.204 |
| -15℃ | 1.182 |
| -10℃ | 1.161 |
| -5℃ | 1.143 |
| 0℃ | 1.127 |
| 5℃ | 1.103 |
| 10℃ | 1.079 |
| 15℃ | 1.063 |
| 20℃ | 1.047 |
| 30℃ | 1 |
| 35℃ | 0.984 |
| 40℃ | 0.968 |
| 45℃ | 0.952 |
| 50℃ | 0.922 |
| 55℃ | 0.904 |
| 60℃ | 0.891 |
| 65℃ | 0.872 |
| 70℃ | 0.844 |
| Altitude-Capacity Reduction Factor Table | ||||
| Altitude (m) | 2000 | 3000 | 4000 | 5000 |
| Rated Operating Current Factor | 1 | 0.96 | 0.91 | 0.86 |
| Rated Operating Voltage Factor | 1 | 1 | 1 | 1 |
| Rated Power Frequency Withstand Voltage Factor | 1 | 0.9 | 0.82 | 0.71 |
| Rated Impulse Withstand Voltage Factor | 1 | 0.9 | 0.82 | 0.71 |
| Rated Ultimate Short-circuit Breaking Capacity & Electrical Endurance Factor | 1 | 0.82 | 0.7 | 0.6 |
| MCB Side-by-Side Installation Derating Factor Table | |||||
| Number of MCBs | 1 | 2~3 | 4~5 | 6~8 | 9~10 |
| Factor for In ≤ 25A | 1 | 0.96 | 0.9 | 0.8 | 0.7 |
| Factor for 32A ≤ In ≤ 63A | 1 | 0.92 | 0.8 | 0.7 | 0.6 |
| Factor for 80A ≤ In ≤ 125A | 1 | 0.9 | 0.8 | 0.7 | / |
Appearance and installation dimensions

DC wiring Diagram























Reviews