ETGL(HGL) Series Load Break Switch-Disconnector
The ETGL (HGL) series load break switch-disconnector is a new generation of load disconnect switches developed by our company. Featuring a dual-break, dual-arc-extinguishing-chamber design, they offer high switching capacity, a compact structure, and convenient installation and wiring; they represent the next generation of low-voltage load break switch-disconnector. The ETGL (HGL) series is suitable for 50 Hz AC systems with a rated insulation voltage of 800 V, a rated operating voltage of 400 V, and a rated current up to 3200 A. It is primarily used in power distribution or motor circuits for infrequent switching and isolation of circuits and lines. The product complies with standards GB/T 14048.1 and GB/T 14048.3.
Model and meaning
| ET | GL | – □ | / □ | □ | J | K | □ | H | TM |
| No. | Product Name | Poles | |||||||
| Company Code | Load Break Switch Disconnector | Rated thermal current (A) | 3: 3-pole 4: 4-pole (3-pole + switchable neutral) |
Z: Load-break switch Z1: Front-to-back arrangement Z2: Left-to-right arrangement C: Side-mounted, front-operated load break switch (If not required, leave blank) |
External operation (Internal operation not specified) |
Viewport (No notes required) |
Auxiliary contacts F11: One normally open, one normally closed F22: Two normally open, two normally closed (Leave blank if not required) |
Operations Behind the Cabinet (Note: Not required) |
Transparent (No notes required) |
Scope of Application
The ETGL (HGL) series load break switch-disconnector is a new generation of load disconnect switches developed by our company. Featuring a dual-break, dual-arc-extinguishing-chamber design, they offer high switching capacity, a compact structure, and convenient installation and wiring; they represent the next generation of low-voltage load break switch-disconnector. The ETGL (HGL) series is suitable for 50 Hz AC systems with a rated insulation voltage of 800 V, a rated operating voltage of 400 V, and a rated current up to 3200 A. It is primarily used in power distribution or motor circuits for infrequent switching and isolation of circuits and lines. The product complies with standards GB/T 14048.1 and GB/T 14048.3.
Normal operating conditions
- Ambient Temperature: The upper limit shall not exceed +40° C, the lower limit shall not be less than -5° C, and the average temperature over 24 hours shall not exceed +35° C.
- Altitude: The installation site must be at an altitude of no more than 2,000 m.
- Ambient Conditions: Max. 50% RH at +40 ° C; higher RH allowed at lower temps (e.g., 90% at 20° C). Special measures required for occasional condensation due to temp variations.
- Pollution Level: Level 3
- Installation Requirements: The basic installation requirement for ETGL (HGL) products is vertical installation.
Product Features
- High current capacity, compact size, long creepage distance, and long electrical life;
- Featuring a dual-break, dual-arc-extinguishing-chamber design, it offers high switching capacity and a long isolation distance;
- Features a viewing window that directly displays the open/closed status of the contacts;
- Spring-loaded operating mechanism; no manual operation required; moving and stationary contacts can achieve rapid make and break;
- Compact design, easy wiring, safe and reliable, saving time and effort;
- Available in three-pole and four-pole conffgurations, with options for in-cabinet or out-of-cabinet operation.
Applicable Standards
IEC 60947-6-1 IEC 60947-3 GB/T 14048.11 GB/T14048.3
| One normally open, one normally closed |
11 | NO+NC | Suitable for MG2[ETGL(HGL)], MG2[ETGL(HGL)]C |
| Two normally open, two normally closed |
12 | 2NO+2NC | Suitable for MG2[ETGL(HGL)], MG2[ETGL(HGL)]C, and MG2[ETGL(HGL)]Z |
Shape and size
| Specifications | ETGL(HGL)/J Dimensions and Mounting Dimensions (mm) | ||||||||||||||
| Current | A | B | C | D | E | Φ | J | K | N | P | R | U | ΦX | Y | Z |
| 125A/3 | 140 | 135 | 125 | 27 | 73 | 5.5 | 120 | 65 | 85 | 36 | 18 | 85 | 9 | 25 | 355 |
| 160A/3 | 140 | 135 | 125 | 27 | 73 | 5.5 | 120 | 65 | 85 | 36 | 20 | 85 | 9 | 25 | 355 |
| 125A/4 | 170 | 135 | 125 | 27 | 73 | 5.5 | 150 | 65 | 85 | 36 | 18 | 85 | 9 | 25 | 355 |
| 160A/4 | 170 | 135 | 125 | 27 | 73 | 5.5 | 150 | 65 | 85 | 36 | 20 | 85 | 9 | 25 | 355 |
| 200A/3 | 180 | 170 | 150 | 35 | 84 | 5.5 | 160 | 90 | 115 | 50 | 25 | 110 | 11 | 25 | 365 |
| 250A/3 | 180 | 170 | 150 | 35 | 84 | 5.5 | 160 | 90 | 115 | 50 | 25 | 110 | 11 | 25 | 365 |
| 200A/4 | 230 | 170 | 150 | 35 | 84 | 5.5 | 210 | 90 | 115 | 50 | 25 | 110 | 11 | 25 | 365 |
| 250A/4 | 230 | 170 | 150 | 35 | 84 | 5.5 | 210 | 90 | 115 | 50 | 25 | 110 | 11 | 25 | 365 |
| 315A/3 | 230 | 240 | 180 | 50 | 118 | 7 | 210 | 140 | 145 | 65 | 32 | 160 | 11 | 37 | 440 |
| 400A/3 | 230 | 240 | 180 | 50 | 118 | 7 | 210 | 140 | 145 | 65 | 35 | 160 | 11 | 37 | 440 |
| 630A/3 | 230 | 260 | 180 | 50 | 118 | 7 | 210 | 140 | 145 | 65 | 40 | 160 | 13 | 37 | 440 |
| 315A/4 | 290 | 240 | 180 | 50 | 118 | 7 | 270 | 140 | 145 | 65 | 32 | 160 | 11 | 37 | 440 |
| 400A/4 | 290 | 240 | 180 | 50 | 118 | 7 | 270 | 140 | 145 | 65 | 35 | 160 | 11 | 37 | 440 |
| 630A/4 | 290 | 260 | 180 | 50 | 118 | 7 | 270 | 140 | 145 | 65 | 40 | 160 | 13 | 37 | 440 |











Reviews