DZ47-63V1 Automatic Reset Overvoltage And Undervoltage Protector
Model and meaning
| DZ47 | 63 | V1 | 63A |
| No. | Design Number | Rated current | |
| Company Code | Design Number | Overvoltage Undervoltage |
20A 25A 32A 40A 50A 63A |
Main Technical Specifications
| Specifications Model | DZ47-63V1 2P | ||||
| Rated AC voltage | 220V | ||||
| Frequency | 50Hz | ||||
| Maximum current | 20A | 32A | 40A | 50A | 63A |
| Maximum power handling | 4.4KVA | 6.6KVA | 8.8KVA | 11 KVA | 13.8KVA |
| Overvoltage trip threshold | 260~275VAC | ||||
| Overvoltage recovery value | 248 ± 5VAC | ||||
| Undervoltage trip threshold | 170 ± 5VAC | ||||
| Undervoltage recovery value | 183 ± 5VAC | ||||
| Delay in power restoration after a power outage | 1–5 minutes | ||||
| Power consumption | ≤ 2W | ||||
| Service life of electrical machinery | ≥ 90,000 times | ||||
| Appearance | 85 mm × 36 mm × 66.5 mm (L × W × H) | ||||
| Specifications Model | DZ47-63V1 4P | ||||||
| Rated AC voltage | 380V | ||||||
| Rated AC voltage | 50Hz | ||||||
| Maximum current | 16A | 20A | 32A | 40A | 50A | 63A | 80A |
| Overvoltage trip threshold | 460±15VAC | ||||||
| Undervoltage trip threshold | 300±15VAC | ||||||
| Delay in power restoration after a power outage | 1–5 minutes | ||||||
| Power consumption | ≤ 2W | ||||||
| Service life of electrical machinery | ≥ 90,000 times | ||||||
| Appearance | 108 mm × 85 mm × 66.5 mm (L × W × H) | ||||||
Shape and size







Reviews
There are no reviews yet.