Applicable Scope
ETZBLE RCBO is applied in the power system of AC 50Hz, single phase 230V, three phases 400v. When somebody gets and electric shock or the residual current exceeds the default value, the RCBO can cut off the power automatically to protect the personal safety and prevent the equipment from the fault resulted from the residual current. It also can protect the circuit against overload and short circuit or can be used for the unfrequent switch of the circuit undernormal condition. And extra protection functions like over voltage, under voltage can be added according to customers’ request.
It conforms to the standard IEC61009-1.GB16917.1.
Model And Meanings

Characteristic
![]() |
![]() |
![]() |
| Compact Size | Short Circuit Protection | Overload Protection |
![]() |
![]() |
![]() |
| Earth leakage protection | Arc Fault Protection | Short arcing |
![]() |
![]() |
![]() |
| High Breaking Capacity | Flame Retardant Material | Complete accessories |
Multi-Machine Side-By-Side Installation Correction Factor
| Pole | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | >9 |
| Factor | 1 | 0.9 | 0.85 | 0.8 | 0.75 | 0.73 | 0.7 | 0.68 | 0.65 | 0.65 |
Technical Parameters
| Shell level rated current Inm(A) | Pole | Rated voltage(V) | Rated current(A) | Rated short circuit breaking capacity Icno(A) |
| 63 | 1P+N | 230/400(220/380) | 6、10、16、20、25、32、40、50、63 | 6000 |
| 2P | ||||
| 3P | 400 | |||
| 3P+N | ||||
| 4P |
| Rated residual current breaking current IΔn(mA) | Rated residual current no breaking current IΔn(mA) | Trip time |
| 10 | 5 | ≤0.1S |
| 30 | 15 | |
| 50 | 25 | |
| 75 | 37.5 | |
| 100 | 50 |
Current Release Character Diagram
| Test current | Rated current | Requested time | Result | Start station | Remark |
| 1.13In | All | t ≤ 1h | Don’t trip | Cool | 6000 |
| 1.45In | All | t<1h | Trip | Heat | Current ascends the requested value stably in 5s |
| 2.55In | In<32A | 1s<t<60s | Trip | Cool | Auxiliary switch closed and power on |
| 2.55In | In>32A | 1s<t<120s | Trip | ||
| 3In (B Type) | All | t ≤ 0.1s | Don’t trip | ||
| 5In (B Type) | t<0.1s | Trip | |||
| 5In (C Type) | t ≤ 0.1s | Don’t trip | |||
| 10In (C Type) | t<0.1s | Trip | |||
| 10In (D Type) | t ≤ 0.1s | Don’t trip | |||
| 14In (D Type) | t<0.1s | Trip |
Appearance and installation dimensions
| Pole | 1P+N | 2P | 3P | 3P+N | 4P |
| Big shell | 54 | 72 | 104 | 118 | 136 |
| Small shell | 45 | 63 | 90 | 99 | 117 |























Reviews