Model And Meanings

Characteristic
![]() |
![]() |
![]() |
![]() |
| Short Circuit Protection | Overload Protection | Earth leakage protection | Arc protection |
![]() |
![]() |
![]() |
![]() |
| Flame Retardant Material | Short arcing | High Breaking Capacity | Multiple Wiring Options |
Technical Parameters
| Item | Parameter |
| Standard | IEC/EN61009-1、IEC/EN62606、GB/T16917.1、GB/T31143 |
| Pole | 1P+N(Two Pole 36mm Width) |
| Rated Working Voltage Ue | AC230/240V |
| Maximum current of the shell frame | 63A |
| Rated Current In | 6A、10A、16A、20A、25A、32A、40A、50A、63A |
| Rated Insulation Voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Rated residual operating current I△n | 10mA、30mA、50mA、100mA、300mA |
| Rated residual non-operating current | 0.5I△n |
| Rated Frequency | 50/60Hz |
| Type of residual current protection | A Type、AC Type |
| Rated residual current breaking capacity I△m | 3000A |
| Tripping Type | Thermomagnetic |
| Instant release type | B Type、C Type |
| Rated short-circuit capacity Icn | 10000A |
| Operational Breaking Capacity Ics | 7500A |
| Electrical Life | |
| Actual Average Value | ≥ 3000 times |
| Standard Specified Value | 2000 times |
| Mechanical Life | |
| Actual Average Value | ≥ 4000 times |
| Standard Specified Value | In ≤ 25A 2000 times |
| In > 25A 1000 times | |
| Overvoltage category | III |
| Pollution degree | 3 |
| Protection Level | IP40; Wiring port IP20 |
| Wiring Capacity | 1.0~16mm² |
| Wiring Torque | 3Nm |
| Operating Ambient Temperature | -25°C~+70°C |
| Storage Ambient Temperature | -35°C~+80°C |
| Installation Method | DIN35 |
| Altitude | ≤ 2000m |
| Weight | 0.19kg/Piece |
| Dimension | |
| Length | 85mm |
| Width | 36mm (1P+N) |
| Height | Max 79mm |
| Package | |
| Pcs/Box | 6 |
| Box /Carton | 10 |
| Storage | The product should be stored in a well-ventilated warehouse, with relative humidity not exceeding 80%, and the ambient temperature should be between -40°C and +80°C. Additionally, there should be no acidic, alkaline, or corrosive gases present. |
Features

b Fault indication
1. when the circuit breaker trips due to leakage or arc fault, the indicator button will pop up. Please press the button before closing.
2.indicator status:
①The red light is always on when the power is turned on normally; the red light flashes for 3 seconds and then turns off when the power is turned off normally.
②When the MCB is closed again after tripping due to Arc fault, the red light flashes for about 10 seconds and then returns to a constant red light.
③When the MCB is closed again tripping due to Leakage fault, the green light flashes for about 10 seconds and then returns to a constant red light.
Circuit Diagram

Appearance and installation dimensions