ETM2L PV On-Grid Circuit Breaker – Molded Case Type

The ETM2L Series PV On-Grid Low-Voltage Circuit Breaker (hereinafter referred to as the CircuitBreaker) is a low-voltage circuit breaker specifically designed for distributed PV power grid connection.Integrating an electric actuator, an intelligent controller, and a molded case circuit breaker, it’ sintended to protect circuits or electrical equipment from overcurrent, short circuit, open phase,undervoltage, voltage loss and more.The Circuit Breaker can achieve undervoltage delayed tripping and avoid voltage fluctuations andsudden drops in power systems, ensuring that the PV power supply does not immediately leave thegrid when there are voltage fluctuations, and maximizing the support role of distributed PV powersupply on the grid. At the same time, it can also enable users to achieve the maximum economic benefits.

Scope of Application

The ETM2L Series PV On-Grid Low-Voltage Circuit Breaker (hereinafter referred to as the CircuitBreaker) is a low-voltage circuit breaker specifically designed for distributed PV power grid connection.Integrating an electric actuator, an intelligent controller, and a molded case circuit breaker, it’ sintended to protect circuits or electrical equipment from overcurrent, short circuit, open phase,undervoltage, voltage loss and more.The Circuit Breaker can achieve undervoltage delayed tripping and avoid voltage fluctuations andsudden drops in power systems, ensuring that the PV power supply does not immediately leave thegrid when there are voltage fluctuations, and maximizing the support role of distributed PV powersupply on the grid. At the same time, it can also enable users to achieve the maximum economic benefits.

The Circuit Breaker is included with an electric actuator, which can achieve automatic closing onvoltage detected, effectively improving the automation performance of distributed PV distributionsystems. The Circuit Breaker is equipped with an RS485 serial interface, which can meet therequirements of communication networking.

Standard

GB 14048.2: Low-voltage switchgear and controlgear Part 2 Circuit-breakersQ/GDW 1972-2013: Technical specifications for low-voltage circuit-breakers for distributedgrid-connected PV stations

GB/T22710: Electronic controllers for low-voltage circuit breakers

GB/T 2423.1: Environmental testing for electric and electronic products Part 2: Testmethod – Tests A: Cold

GB/T 2423.2: Environmental testing for electric and electronic products – Part 2: Testmethod Tests B: Dry heat

Dimensions(mm)

Model Overall Dimensions Installing Dimensions
L W T W×L ΦD
125AF 220 122 138 60×200 Φ4.5
250AF 240 142 137 70×202 Φ4.5
400AF 337 198 186 96×274 Φ8
630AF 337 198 186 96×274 Φ8
800AF 370 280 190 140×333 Φ8

Technical Parameters

                 Item/Parameter
Level/Spec
ETM2L-125M/3N ETM2L-250M/3N ETM2L-400M/3N ETM2L-630M/3N ETM2L-800M/3N
Frame Current (A) 125 250 400 630 800
Number of Poles 3P+N
Rated Working Voltage Ue (V) AC400 / 50HZ
Rated Insulation Voltage Ui (V) AC800
Rated Impulse Withstand Voltage Uimp 8kW
Flashover Distance (mm) 50 50 100 100 100
Limit Short Circuit Breaking Capacity Icu (kA) 50 50 75 75 65
Operating Short Circuit Breaking Capacity Ics (kA) 35 35 50 50 42
Use Category B A B B B
Rated Short Time Withstand Current Icw (kA / 1s) 5/1S 5/1S 10/1S 10/1S 10/1S
Automatic Closing Time (s) 25~30
Overvoltage Protection Value (V) ※ 253-300V, with delay adjustable
Undervoltage Protection Value (V) ※ 154-187, with a delay of 0-10 seconds, adjustable at one gear per second
Total Number of Operations 10000 8000 5000
Trip on Power Outage ※ A delay of 0-10 seconds, adjustable at one gear per second
Restore Voltage ※ 185-276V
Overload Protection
Short Circuit Protection
Residual Current Protection
Close on Voltage Detected
Open Phase Protection
Overvoltage/Undervoltage Protection

 Overall Dimension Diagram (mm)

 

Reviews

There are no reviews yet.

Be the first to review “ETM2L PV On-Grid Circuit Breaker – Molded Case Type”

Your email address will not be published. Required fields are marked *