Applicable Scope
ETBLE-63 RCB0 is suitable to the single phase residual circuit of 50/60Hz, rated voltage 230v, as the current leakage protection and protect the civil electrical circuit from over load and short circuit and it has the features of volume small, breaking capacity high. Null/live wire is cut at the same time, and even the wire is reverse connection,it still have current leakage Protection. The product conforms to standards IEC1009.1,GB16917.1etc.
Model And Meanings

Characteristic
![]() |
![]() |
![]() |
| Compact Size | Short Circuit Protection | Overload Protection |
![]() |
![]() |
![]() |
| Earth leakage protection | Arc Fault Protection | Short arcing |
![]() |
![]() |
![]() |
| High Breaking Capacity | Flame Retardant Material | Complete accessories |
Breaking Characteristic Curve

Technical Parameters
| Rated voltage(V) | Pole | Shell-level rated current(A) | Rated current(A) | Rated breaking residual current(mA) |
| 230(220) | 1P+N | 63A | 6,10,16,20,25,32 | 30 |
| 50,63 |
| Rated not breaking residual current(mA) | Breaking time of rated residual current(s) | Breaking Capacity(A) | Overvoltage action value | Undervoltage action value |
| 15 | ≤ 0.1 | 6000 | 280V±5V | 170V±5V |
| 4000 |
Remark: wiring is terminal with clamp, cable dia.: 10mm² below available for hard cable.
Current Release Character Diagram
| Test current | Rated current | Requested time |
| 1.13In | All | t ≤ 1h |
| 1.45In | t < 1h | |
| 2.55In | 1s < t < 60s | |
| 5In | t ≤ 0.1s | |
| 10In | t < 0.1s |
| Result | Start station | Remark |
| Don’t trip | Cool | |
| Trip | Heat | Current ascends the requested value stably in 5s |
| Trip | Cool | Auxiliary switch closed and power on |
| Don’t trip | Cool | |
| Trip | Cool |