ETGL(HGL) Series Load Break Switch-Disconnector

The ETGL (HGL) series load break switch-disconnector is a new generation of load disconnect switches developed by our company. Featuring a dual-break, dual-arc-extinguishing-chamber design, they offer high switching capacity, a compact structure, and convenient installation and wiring; they represent the next generation of low-voltage load break switch-disconnector. The ETGL (HGL) series is suitable for 50 Hz AC systems with a rated insulation voltage of 800 V, a rated operating voltage of 400 V, and a rated current up to 3200 A. It is primarily used in power distribution or motor circuits for infrequent switching and isolation of circuits and lines. The product complies with standards GB/T 14048.1 and GB/T 14048.3.

Model and meaning

ET GL – □ / □ J K H TM
No. Product Name Poles
Company Code Load Break Switch Disconnector Rated thermal current (A) 3: 3-pole
4: 4-pole
(3-pole + switchable neutral)
Z: Load-break switch
Z1: Front-to-back arrangement
Z2: Left-to-right arrangement
C: Side-mounted, front-operated load break switch
(If not required, leave blank)
External operation
(Internal operation not specified)
Viewport
(No notes required)
Auxiliary contacts
F11: One normally open, one normally closed
F22: Two normally open, two normally closed
(Leave blank if not required)
Operations Behind the Cabinet
(Note: Not required)
Transparent
(No notes required)

Scope of Application

The ETGL (HGL) series load break switch-disconnector is a new generation of load disconnect switches developed by our company. Featuring a dual-break, dual-arc-extinguishing-chamber design, they offer high switching capacity, a compact structure, and convenient installation and wiring; they represent the next generation of low-voltage load break switch-disconnector. The ETGL (HGL) series is suitable for 50 Hz AC systems with a rated insulation voltage of 800 V, a rated operating voltage of 400 V, and a rated current up to 3200 A. It is primarily used in power distribution or motor circuits for infrequent switching and isolation of circuits and lines. The product complies with standards GB/T 14048.1 and GB/T 14048.3.

Normal operating conditions

  • Ambient Temperature: The upper limit shall not exceed +40° C, the lower limit shall not be less than -5° C, and the average temperature over 24 hours shall not exceed +35° C.
  • Altitude: The installation site must be at an altitude of no more than 2,000 m.
  • Ambient Conditions: Max. 50% RH at +40 ° C; higher RH allowed at lower temps (e.g., 90% at 20° C). Special measures required for occasional condensation due to temp variations.
  • Pollution Level: Level 3
  • Installation Requirements: The basic installation requirement for ETGL (HGL) products is vertical installation.

Product Features

  • High current capacity, compact size, long creepage distance, and long electrical life;
  • Featuring a dual-break, dual-arc-extinguishing-chamber design, it offers high switching capacity and a long isolation distance;
  • Features a viewing window that directly displays the open/closed status of the contacts;
  • Spring-loaded operating mechanism; no manual operation required; moving and stationary contacts can achieve rapid make and break;
  • Compact design, easy wiring, safe and reliable, saving time and effort;
  • Available in three-pole and four-pole conffgurations, with options for in-cabinet or out-of-cabinet operation.

Applicable Standards

IEC 60947-6-1 IEC 60947-3 GB/T 14048.11 GB/T14048.3

One normally open, one
normally closed
11 NO+NC Suitable for MG2[ETGL(HGL)], MG2[ETGL(HGL)]C
Two normally open, two
normally closed
12 2NO+2NC Suitable for MG2[ETGL(HGL)], MG2[ETGL(HGL)]C, and
MG2[ETGL(HGL)]Z

Shape and size

Specifications ETGL(HGL)/J Dimensions and Mounting Dimensions (mm)
Current A B C D E Φ J K N P R U ΦX Y Z
125A/3 140 135 125 27 73 5.5 120 65 85 36 18 85 9 25 355
160A/3 140 135 125 27 73 5.5 120 65 85 36 20 85 9 25 355
125A/4 170 135 125 27 73 5.5 150 65 85 36 18 85 9 25 355
160A/4 170 135 125 27 73 5.5 150 65 85 36 20 85 9 25 355
200A/3 180 170 150 35 84 5.5 160 90 115 50 25 110 11 25 365
250A/3 180 170 150 35 84 5.5 160 90 115 50 25 110 11 25 365
200A/4 230 170 150 35 84 5.5 210 90 115 50 25 110 11 25 365
250A/4 230 170 150 35 84 5.5 210 90 115 50 25 110 11 25 365
315A/3 230 240 180 50 118 7 210 140 145 65 32 160 11 37 440
400A/3 230 240 180 50 118 7 210 140 145 65 35 160 11 37 440
630A/3 230 260 180 50 118 7 210 140 145 65 40 160 13 37 440
315A/4 290 240 180 50 118 7 270 140 145 65 32 160 11 37 440
400A/4 290 240 180 50 118 7 270 140 145 65 35 160 11 37 440
630A/4 290 260 180 50 118 7 270 140 145 65 40 160 13 37 440