ETZM High Voltage Molded Case Circuit Breaker

Scope of Application

The ETEM Series High Voltage Molded Case Circuit Breaker (hereinafter referred to as the Circuit Breaker) is suitable for distribution network circuits with AC 50Hz, rated insulation voltage 1140V, rated working volatge 1140V, and rated working current from6A to 800A. It’ s used to distribute electricity and protect circuits and power equipmentfrom overload, short circuit, undervoltage, and other faults. It can also protect motorsagainst infrequent starting, overload, short circuit, and undervoltage. This Circuit Breakerfeatures, among others, small size, high breaking, and short flashover, making it anideal product for users. The Circuit Breaker can be installed either vertically (i.e. verticalinstallation) or horizontally (horizontal installation). The wiring method is optional forfront panel wiring, rear panel wiring, or plug-in wiring.

Working Environment

  • The upper limit value of ambient air temperature shall not exceed +40 °C, and its lowerlimit value shall not be less than -5 °C;
  • Pollution level: 3;
  • Protection rating: IP20;
  • The altitude of the installation site should not exceed 2,000m;
  • The RH of the atmosphere should not exceed 50% at the highest ambient temperature of+40 °C. At lower temperatures, there can be higher Rh, such as 90% at 20 °C. Necessarymeasures should be taken in consideration of the condensation that occurs on theproduct due to temperature changes.

Electrical Technical Parameters

Basic Parameters of Thermal Magnetic / Leakage Type

Model ETZM-250 ETZM-320
Frame Rating Current (A) 250 320
Rated Current ln(A) 63、100、125、160
180、200、225、250
250、315、320
Number of Poles 3
Rated Insulation Voltage Ui (V) AC1150
Rated Working Voltage Ue (V) AC800V AC1140V AC800V AC1140V
Rated Impulse Withstand Voltage Uimp (V) 8000 8000
Flashover Distance (mm) 0 0
Limit Short Circuit
Breaking Capacity
lcu (kA)
M 36.5 15 36.5 15
H 50 15 50 15
Operating Short Circuit
Breaking
Capacity lcs (kA)
M 36.5 15 36.5 15
H 50 15 50 15
Leakage Operating Current I△n (mA)
Leakage Non-operating Current I△n (mA)
Mechanical/
Electrical Life
(Operations)
Power on 10000
Power of 10000
ETZM-400 ETZM-630 ETZM-800
400 630 800
315、320、350、400 400、500、630 400、500、630、800
AC800V AC1140V AC800V AC1140V AC800V AC1140V
12000 12000 12000
0 0 0
H 36.5 10 36.5 10 36.5 10
R 50 15 50 15 50 15
H 36.5 10 36.5 10 36.5 10
R 50 15 50 15 50 15
10000
10000

Attachment Type

                    Attachment Name
Attachment Code
No Attachments Alarm Contact Shunt Tripper Auxiliary Contact Undervoltage Tripper Auxiliary Contact of Shunt Tripper Tripper Contact of Shunt Tripper Two Sets of Auxiliary Contacts
Electromagnetic Tripper 200 208 210 220 230 240 250 260
Duplex Tripper 300 308 310 320 330 340 350 360
                    Attachment Name
Attachment Code
No Attachments Alarm Contact Shunt Tripper Auxiliary Contact Undervoltage Tripper Auxiliary Contact of Shunt Tripper Tripper Contact of Shunt Tripper Two Sets of Auxiliary Contacts
Electromagnetic Tripper 370 218 228 238 248 240 268 278
Duplex Tripper 270 218 228 238 248 340 268 278

 