ETZM High Voltage Molded Case Circuit Breaker
Scope of Application
The ETEM Series High Voltage Molded Case Circuit Breaker (hereinafter referred to as the Circuit Breaker) is suitable for distribution network circuits with AC 50Hz, rated insulation voltage 1140V, rated working volatge 1140V, and rated working current from6A to 800A. It’ s used to distribute electricity and protect circuits and power equipmentfrom overload, short circuit, undervoltage, and other faults. It can also protect motorsagainst infrequent starting, overload, short circuit, and undervoltage. This Circuit Breakerfeatures, among others, small size, high breaking, and short flashover, making it anideal product for users. The Circuit Breaker can be installed either vertically (i.e. verticalinstallation) or horizontally (horizontal installation). The wiring method is optional forfront panel wiring, rear panel wiring, or plug-in wiring.
Working Environment
- The upper limit value of ambient air temperature shall not exceed +40 °C, and its lowerlimit value shall not be less than -5 °C;
- Pollution level: 3;
- Protection rating: IP20;
- The altitude of the installation site should not exceed 2,000m;
- The RH of the atmosphere should not exceed 50% at the highest ambient temperature of+40 °C. At lower temperatures, there can be higher Rh, such as 90% at 20 °C. Necessarymeasures should be taken in consideration of the condensation that occurs on theproduct due to temperature changes.
Electrical Technical Parameters
Basic Parameters of Thermal Magnetic / Leakage Type
| Model | ETZM-250 | ETZM-320 | |||
| Frame Rating Current (A) | 250 | 320 | |||
| Rated Current ln(A) | 63、100、125、160 180、200、225、250 |
250、315、320 | |||
| Number of Poles | 3 | ||||
| Rated Insulation Voltage Ui (V) | AC1150 | ||||
| Rated Working Voltage Ue (V) | AC800V | AC1140V | AC800V | AC1140V | |
| Rated Impulse Withstand Voltage Uimp (V) | 8000 | 8000 | |||
| Flashover Distance (mm) | 0 | 0 | |||
| Limit Short Circuit Breaking Capacity lcu (kA) |
M | 36.5 | 15 | 36.5 | 15 |
| H | 50 | 15 | 50 | 15 | |
| Operating Short Circuit Breaking Capacity lcs (kA) |
M | 36.5 | 15 | 36.5 | 15 |
| H | 50 | 15 | 50 | 15 | |
| Leakage Operating Current I△n (mA) | — | — | — | — | |
| Leakage Non-operating Current I△n (mA) | — | — | — | — | |
| Mechanical/ Electrical Life (Operations) |
Power on | 10000 | |||
| Power of | 10000 | ||||
| ETZM-400 | ETZM-630 | ETZM-800 | ||||
| 400 | 630 | 800 | ||||
| 315、320、350、400 | 400、500、630 | 400、500、630、800 | ||||
| AC800V | AC1140V | AC800V | AC1140V | AC800V | AC1140V | |
| 12000 | 12000 | 12000 | ||||
| 0 | 0 | 0 | ||||
| H | 36.5 | 10 | 36.5 | 10 | 36.5 | 10 |
| R | 50 | 15 | 50 | 15 | 50 | 15 |
| H | 36.5 | 10 | 36.5 | 10 | 36.5 | 10 |
| R | 50 | 15 | 50 | 15 | 50 | 15 |
| — | — | — | — | — | — | |
| — | — | — | — | — | — | |
| 10000 | ||||||
| 10000 | ||||||
Attachment Type
| Attachment Name Attachment Code |
No Attachments | Alarm Contact | Shunt Tripper | Auxiliary Contact | Undervoltage Tripper | Auxiliary Contact of Shunt Tripper | Tripper Contact of Shunt Tripper | Two Sets of Auxiliary Contacts |
| Electromagnetic Tripper | 200 | 208 | 210 | 220 | 230 | 240 | 250 | 260 |
| Duplex Tripper | 300 | 308 | 310 | 320 | 330 | 340 | 350 | 360 |
| Attachment Name Attachment Code |
No Attachments | Alarm Contact | Shunt Tripper | Auxiliary Contact | Undervoltage Tripper | Auxiliary Contact of Shunt Tripper | Tripper Contact of Shunt Tripper | Two Sets of Auxiliary Contacts |
| Electromagnetic Tripper | 370 | 218 | 228 | 238 | 248 | 240 | 268 | 278 |
| Duplex Tripper | 270 | 218 | 228 | 238 | 248 | 340 | 268 | 278 |