ETM1L Series Molded Case Residual Current Circuit Breakers
The ETM1L series residual current circuit breakers (hereinafter referred to as “circuit breakers”) are primarily designed for use in AC 50 Hz, with a rated operating voltage of 400 V and a rated current up to 800 A. They are used to provide indirect contact protection for personnel, prevent ffre hazards caused by ground fault currents resulting from equipment insulation failure, distribute electrical energy, and protect power supply equipment from overloads and short circuits. They may also be used for infrequent switching of circuits and infrequent starting of motors.
Scope of Application
The ETM1L series residual current circuit breakers (hereinafter referred to as “circuit breakers”) are primarily designed for use in AC 50 Hz, with a rated operating voltage of 400 V and a rated current up to 800 A. They are used to provide indirect contact protection for personnel, prevent ffre hazards caused by ground fault currents resulting from equipment insulation failure, distribute electrical energy, and protect power supply equipment from overloads and short circuits. They may also be used for infrequent switching of circuits and infrequent starting of motors.
Applicable Standards
IEC 60947-2 GB/T 14048.2
Note: When placing an order, customers must clearly specify the circuit breaker model, speciffcations, and included accessories. When using undervoltage trip units or shunt trip units, the operating voltage (or control power supply voltage) must be speciffed.
For example: 1. To order an ETM1L-125M four-pole circuit breaker for power distribution with a rated current of 50A, “0” arc suppression, a manual operating mechanism, a shunt trip unit (AC380V), auxiliary contacts, alarm contacts, and 20 rear-panel terminals: The order should be written as: ETM1L-125MZ/4348, In=50A, “0” arc, shunt trip unit AC380V, rear panel wiring, 20 units.
Model and meaning
| ETM1L | 125 | L | P |
| Name | Frame Grade | Breaking Capacity Code |
Operation Mode Code |
| ETM1L Series Molded Case Residual Current Circuit Breaker |
125 250 400 630 800 |
L M H |
Direct control via joystick (no code) P: Electric operation Z: Controller operation |
| 3 | 3 | 10 | 2 | 100 |
| Poles | Name of the trip device | Attachment Code | Purpose Code | Rated current |
| 2P 3P 4P |
2: Electromagnetic trip unit 3: Double-pole trip unit 0: No protection (For isolation only) |
Attachment Code | Circuit breakers used for power distribution have no code; circuit breakers used to protect motors are designated by the number 2. |
10A~800A |
MainTechnical Speciffcations
| Model No. | ETM1L-125L | ETM1L-125M | ETM1L-125H | ETM1L-125L | ETM1L-125H | ETM1L-125M | ETM1L-400L | ETM1L-400M | ETM1L-400H | ETM1L-630L | ETM1L-630M | ETM1L-630H | ETM1L-800L | ETM1L-800M | ETM1L-800H | |
| Poles | 2 | 3 | 4 | 2 | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | ||||
| Rated current In(A) | 10、16、20、25、32、40、 50、63、80、100、125 |
100、125、160、180、200、225、 250 |
225、250、315、350、400 | 400、500、630 | 630、700、800 | |||||||||||
| Rated operating voltage (V) | 400 | |||||||||||||||
| Rated short circuit breaking capacity |
Icu(kA) | 35 | 50 | 85 | 35 | 50 | 85 | 50 | 65 | 100 | 50 | 70 | 100 50 | 70 | 100 | |
| Ics(kA) | 25 | 35 | 50 | 25 | 35 | 50 | 25 | 35 | 50 | 25 | 35 | 50 25 | 35 | 50 | ||
| Rated residual operating current I △ no(mA) |
30/100/300 (Non-delayed) |
100/300/500 (Delay-type) |
100/300/500 | 100/300/500 | 100/300/500 | 100/300/500 | ||||||||||
| Maximum interruption time (s) |
≤ 0.1 (Non-delayed) |
≤ 0.1/0.4/1 (Delay-type) |
≤ 0.1/0.4/1 | ≤ 0.1/0.4/1 | ≤ 0.1/0.4/1 | ≤ 0.1/0.4/1 | ||||||||||
| Arc length (mm) | ≤ 50 | ≤ 100 | ||||||||||||||
| Dimensions (mm) |
Length L | 150 | 165 | 257 | 280 | 280 | ||||||||||
| Width W | 62 | 92 | 122 | 75 | 107 | 142 | 150 | 198 | 210 | 280 | 210 | 280 | ||||
| Highth H | 94 | 110 | 94 | 110 | 146 | 155 | 155 | |||||||||