ETM1L Series Molded Case Residual Current Circuit Breakers

The ETM1L series residual current circuit breakers (hereinafter referred to as “circuit breakers”) are primarily designed for use in AC 50 Hz, with a rated operating voltage of 400 V and a rated current up to 800 A. They are used to provide indirect contact protection for personnel, prevent ffre hazards caused by ground fault currents resulting from equipment insulation failure, distribute electrical energy, and protect power supply equipment from overloads and short circuits. They may also be used for infrequent switching of circuits and infrequent starting of motors.

Scope of Application

The ETM1L series residual current circuit breakers (hereinafter referred to as “circuit breakers”) are primarily designed for use in AC 50 Hz, with a rated operating voltage of 400 V and a rated current up to 800 A. They are used to provide indirect contact protection for personnel, prevent ffre hazards caused by ground fault currents resulting from equipment insulation failure, distribute electrical energy, and protect power supply equipment from overloads and short circuits. They may also be used for infrequent switching of circuits and infrequent starting of motors.

Applicable Standards

IEC 60947-2 GB/T 14048.2

Note: When placing an order, customers must clearly specify the circuit breaker model, speciffcations, and included accessories. When using undervoltage trip units or shunt trip units, the operating voltage (or control power supply voltage) must be speciffed.

For example: 1. To order an ETM1L-125M four-pole circuit breaker for power distribution with a rated current of 50A, “0” arc suppression, a manual operating mechanism, a shunt trip unit (AC380V), auxiliary contacts, alarm contacts, and 20 rear-panel terminals: The order should be written as: ETM1L-125MZ/4348, In=50A, “0” arc, shunt trip unit AC380V, rear panel wiring, 20 units.

Model and meaning

ETM1L 125 L P
Name Frame Grade Breaking
Capacity Code
Operation Mode
Code
ETM1L Series
Molded Case
Residual
Current
Circuit
Breaker
125
250
400
630
800
L
M
H
Direct control via
joystick (no code)
P: Electric operation
Z: Controller
operation
3 3 10 2 100
Poles Name of the trip device Attachment Code Purpose Code Rated current
2P
3P
4P
2: Electromagnetic trip
unit
3: Double-pole trip unit
0: No protection
(For isolation only)
Attachment Code Circuit breakers
used for power
distribution have
no code; circuit
breakers used to
protect motors are
designated by the
number 2.
10A~800A

MainTechnical Speciffcations

Model No. ETM1L-125L ETM1L-125M ETM1L-125H ETM1L-125L ETM1L-125H ETM1L-125M ETM1L-400L ETM1L-400M ETM1L-400H ETM1L-630L ETM1L-630M ETM1L-630H ETM1L-800L ETM1L-800M ETM1L-800H
Poles 2 3 4 2 3 4 3 4 3 4 3 4
Rated current In(A) 10、16、20、25、32、40、
50、63、80、100、125
100、125、160、180、200、225、
250
225、250、315、350、400 400、500、630 630、700、800
Rated operating voltage (V) 400
Rated short circuit
breaking capacity
Icu(kA) 35 50 85 35 50 85 50 65 100 50 70 100            50 70 100
Ics(kA) 25 35 50 25 35 50 25 35 50 25 35 50             25 35 50
Rated residual
operating current
I △ no(mA)
30/100/300
(Non-delayed)
100/300/500
(Delay-type)
100/300/500 100/300/500 100/300/500 100/300/500
Maximum interruption
time (s)
≤ 0.1
(Non-delayed)
≤ 0.1/0.4/1
(Delay-type)
≤ 0.1/0.4/1 ≤ 0.1/0.4/1 ≤ 0.1/0.4/1 ≤ 0.1/0.4/1
Arc length (mm) ≤ 50 ≤ 100
Dimensions
(mm)
Length L 150 165 257 280 280
Width W 62 92 122 75 107 142 150 198 210 280 210 280
Highth H 94 110 94 110 146 155 155

 