ETW3 Series Intelligent Air Circuit Breakers

Applicable StandardsIEC

60947-2 GB/T 14048.2

Model and meaning

ETW3
Name
Intelligent Air
Molded Case
Circuit Breakers
1600 3P 630
Frame Grade Poles Rated current
1600 3P
4P
200、400、630、800、1000、1250、1600
2000 3P 630
Frame Grade Poles Rated current
2000
3200
4000
6300
3P
4P
2000:
630、800、1000、
1250、1600、2000
3200:
2000、2500、2900、
3200
4000:
3200、3600、4000
6300:
4000、5000、6300
M、H AC230 1
Smart Controller Code Control loop supply voltage Other configurations
M: Standard Smart Model
H: (Advanced) Smart Model for Communication
AC230: 230V AC
AC400: 400V AC
DC220: 220V DC
DC110: 110V DC
1. Undervoltage time-delay trip unit
2.Undervoltage instantaneous trip unit
3. Phase separator
4. Mechanical interlock (lever)
5. Mechanical interlock (cable)
6. One lock, one key
7. Two locks, one key
8. Three locks, two keys
9.Auxiliary contact configuration
10. Door frame
11. Horizontal wiring
12. Vertical wiring

Main Technical Specifications

Model and frame current ETW3-1600 ETW3-2000 ETW3-3200 ETW3-6300
Rated current In(A) 200/400/630/800/1000/1250/1600 630/800/1000/1250/1600/2000 2000/2500/2900/3200 4000/5000/6300
Neutral-to-ground rated current In(A) 100%In 100%In 100%In 50%In
Rated operating voltage Ue(V) AC400/690
frequency (Hz) 50
Poles 3P/4P
Rated impulse withstand voltage (kV) 12
Rated insulation voltage (V) 1000
Power-frequency withstand voltage (V)1min 2200
Rated short-circuit breaking capacity Icu(kA) AC400V 65 90 100 120
AC690V 55 65 65 100
Rated short-circuit breaking capacity Ics(kA) AC400V 65 75 100 100
AC690V 42 65 65 80
Rated short-time withstand current Icw/1s(kA) AC400V 65 75 100 100
AC690V 42 65 65 80
Operating life (times)
Once for amounts under 2,500/3min
2,500 or more, 1 time/6min
Electrical life 7000 7000 7000 7000
Mechanical life 10000 10000 10000 10000